Position values are being transferred to the encoder,
encoder and serial interface are working.
Encoder is an unknown type and does not support the
required serial communication protocol. Encoder is the
wrong type, i.e. EnDat connected to a HIPERFACE
feedback card. Solution: verify encoder type.
The interface looks at each incremental channel for the
idle voltage value of 2.5V with reference to common (pin
13). If this voltage is not present an error will be triggered
with this fault code. Solution: check all signal connections,
replace cable with new.
The interface looks at each data or clock channel for the
idle voltage value of 2.5V with reference to common (pin
13). If this voltage is not present an error will be triggered
with this fault code. Solution: check all signal connections,
replace cable with new.
The position deviation between the incremental channels
and the absolute values is greater than 2.8 degrees. On
SIN/COS the comparison is made between occurrences of
the zero pulse. Too many or too few counts between the
zero pulse will trigger this error. Normally, this is caused by
a bad encoder cable and/or poor shielding and grounding
of the cable. Solution: replace the cable.
Compares the internal value of ppr stored inside the
encoder with the setting of LF.2. If they do not match
this error code will be activated. Solution: verify correct
encoder ppr and enter it in LF.2.
Interface Card not
recognized
The serial interface card is not recognized by the main
CPU of the drive. Replace the feedback card.
OHEnc
Encoder temp is measure by the encoder and the error is
passed on to the drive via serial com.
Actual speed has exceeded the max speed of the
encoder.
Internal encoder signals are incorrect or out of tolerance.
Replace the encoder
The encoder will be formatted according to the prescribed
structure. This will allow further read/write cycles to
occur.
The feedback card has recognized that a new or different
encoder is now connected to the drive. Therefore
it is necessary to confirm. Reenter the values in
LF.26,LF.2,LF.
Encoder memory not
formatted
Encoder memory structure is not valid and therefore can
not be read
The encoder is busy during data transfer and cannot accept
the transmission.
There is no communication between the encoder and
the drive.