HITACHI WJ200 Drives 150HF User Guide – Manuals+

19/08/2022 admin

0I nspire the Next

WJ200
Quick Start

Quick Start Essential

Parameters

b037 – Unlocks parameters (default 04)
A001 – Frequency (Speed) Source (default 02)
A002 – Run Command Source (default 02)
b012 – Motor nameplate current (default varies)
b091 – Stop Mode (default 00)
H004 – Motor nameplate poles (default 4 poles)
F001 – Keypad Speed setting (default 00.00)
F002 – Acceleration time (default 10 seconds)
F003 – Deceleration time (default 10 seconds)

To Unlock All the Parameters

  1. Press ESC to enter programming mode
  2. Press ESC until parameter b001 is on the display of your drive
  3. Press the UP key until b037 is reached
  4. Then press the SET key to enter the b037 parameter
  5. Now you can change the 04 to 00 using the down key
  6. Press the SET key to save the data Now you have unleashed your WJ200 drive!

To Set the Motor Current

  1. Press ESC to enter programming mode
  2. Press ESC until parameter b001 is on the display of your drive
  3. Press the UP key until b012 is reached
  4. Then press the SET key to enter the b012 parameter
  5. Now you can set your motor nameplate current using the Up and Down keys

  6. Press the SET key to save the data

To Set the Motor Poles

  1. Press ESC to enter programming mode
  2. Press ESC until parameter H001 is on the display of your drive
  3. Press the UP key until H004 is reached
  4. Then press the SET key to enter the H004 parameter
  5. Now you can set the motor poles based on the speed of your motor
  6. Press the SET key to save the data
    Motor poles = 120*60/synchronous speed (1200, 1800, 3600 RPM)

To Set the Speed Reference

  1. Press ESC to enter programming mode
  2. Press ESC until parameter A001 is on the display of your drive
  3. Then press the SET key to enter the A001 parameter
  4. Select the speed reference from the options below
    00- To use the Keypad Potentiometer
    01- Analog input (0- 10Vdc, or 4-20mA) from the terminals
    02- When using the Keypad set the speed with parameter F001
    03- When setting the speed via Modbus communication network
    04- Option card used for speed
    06- If your application is using a pulse train input
    07- When setting the speed via the Easy Sequence programming
    10- When the speed is a result of an operation used in your drive programming
  5. Press the  SET key to save the data

To Set the Run Command Source

  1. Press ESC to enter programming mode
  2. Press ESC until parameter A001 is on the display of your drive
  3. Press the UP key until A002 is reached
  4. Then press the SET key to enter the A002 parameter
  5. Now you can select the run command source from the options below
    01- To use the digital input via the terminals
    02- When your application calls for using the Keypad to run command
    03- Use this option when commanding your drive to run via your Modbus communication network
    04- Option card used for run
  6. Press the SET key to save the data

To Set the Frequency or Speed

  1. Press ESC to enter programming mode

  2. Press ESC until parameter F001 is on the display of your drive
  3. Then press the SET key to enter the F001 parameter
  4. Now you can adjust the speed of your drive based on your application
  5. Press the SET key to save the data
    F001 parameter can be adjusted with your driver stopped or running.

To Set the Acceleration Time

  1. Press ESC to enter programming mode
  2. Press ESC until parameter F001 is on the display of your drive
  3. Press the UP key until F002 is reached
  4. Then press the SET key to enter the F002 parameter
  5. Now you can adjust the acceleration time of your drive based on your application. The time is adjusted using the Up and Down keys
  6. Finally, press the SET key to save the data

To Set the Deceleration Time

  1. Press ESC to enter programming mode
  2. Press ESC until parameter F001 is on the display of your drive
  3. Press the Up key until F003 is reached
  4. Then press the SET key to enter the F003 parameter
  5. Now you can adjust the deceleration time of your drive based on your application. The time is adjusted using the UP and Down keys
  6. Press the SET key to save the data

To Set the Stop Mode

  1. Press ESC to enter programming mode
  2. Press ESC until parameter b001 is on the display of your drive
  3. Press and hold the UP key until b091 is reached
  4. Then press the SET key to enter the b091 parameter
  5. Now you can select the Stop Mode from the options below
    00- decelerate to stop (controlled stop)
    01- free run stop (coast)
  6. Press the SET key to save the data

TECH SUPPORT
980-500-7141
WEBSITE
https://www.hitachi-iesa.com/ac-drivesinverters
EMAIL
[email protected]

Documents / Resources

Alternate Text Gọi ngay